Hello,
I have a program, Win-911 that calls phone numbers when it is triggered. That part is working thanks to Fodrod and CoralTech; https://www.tek-tips.com/viewthread.cfm?qid=1818199. To acknowledge the alarm I can enter a code on the phone. That part is not working. I enter the code, but...
I changed 84-19-28 Type 2 to G729. I changed 15-05-15 for extension 1899 to Type 2. I changed Win-911 to use the G729 codec. I removed the dialing prefix and used 915555551234 and the test call went out. To recap for future people:
Add your SIP extension using PcPro.
Go to your extension...
I went to 11-02 and set station port 101 to 1899. Station port 100 is a working IP telephone, extension 1100. Station port 102 is extension 1102. There is no extension 1101.
When I try from Win-911 the packet capture shows:
Request: INVITE sip:9,15555551234@10.100.152.11:5070.
Status: 503 Service Unavailable
Request: ACK sip:9,15555551234@10.100.152.11:5070.
The server doesn't have a audio card so I can't test using Microsip. From my computer Microsip works so I...
I am trying microsip. I entered the 10.100.152.11:5070 for the sip server, used 1899 as the username, typed in the password used in 15-05-16, added the dialing prefix 9, set the transport to UDP and clicked save. Microsip says online at this point but it does not do anything. No dial tone, no...
I do have access to PCPro. Now I can see the extension in the list. Attached are the settings that Win-911 is looking for and are available. Win-911 tech support is not helpful in this case as they told me I have to get the information from the phone company. Win-911 has the following codecs...
I went to 11-02 and set station port 101 to 1899. Next I opened 15-01 to set the name and the extension 1899 does not appear in the list of extensions. I then go to 15-05 to try to set a password but again the extension 1899 is not listed. I am sure I forgot something but it has been a long week.
We are using a ISDN circuit provided by AT&T as a part of their IP Flex solution. So SIP on the AT&T side, ISDN port is used on the SV9100. It sounds like ESRI is using a SIP client of some sort based on the feedback from the sales staff I have been speaking with. The SV9100 is running...
I have a SV9100 that whenever ESRI calls me, my phone rings, I pick it up and the line disconnects. This happens every single time they call me. I can call them with no problems. It could be anyone from ESRI, tech support, my rep, it always disconnects. It does not happen any other time that...
I should clarify that the installer is the win911 installer and not the NEC installer. We have a device that monitors a gas level, if the level goes too low this device calls a person to let them know there is a problem. It takes a telephone line so I just plugged it into one of the analog...
Win911 is software that makes phone calls to alert people there is a problem. It uses SIP. I have given the installer the IP address and port number for the NEC SV9100 phone system. Do I have to do anything else? Do I have to add an extension for the computer? The software will only be...
I am actually on site right now. I have full access to everything. I should mention I have a SV9100 running WebPro 11.00.00 and Main Software 11.00.52.
I need to have a recording play for ALL incoming calls today. Basically it is a We are closed due to the inclement weather message. It should play before everything. How can I do this?
I should have started off with that this is my first NEC phone system. I come from a 3Com NBX background. NEC is very different. So I screwed up when I used my phone that has admin permission, went into my voicemail, dialed 72 + 2 + 011 and recorded a test message? I should have dialed his...
47-07 Routing Mailbox 11 is set to Announcement. I recorded a test announcement to 011 from my administrator phone. I went to 22-11 and found the phone number I want to use and put in 4011 for Target 1. When I call the number I don't get the test message. I get the standard 4 rings and leave...
This site uses cookies to help personalise content, tailor your experience and to keep you logged in if you register.