Sorry for my first answer.
It is best to check the power supply of the phone
system first.
If the power supply of the phone system is not able
to work without power for 10 ms then use a so called
true on-line UPS not a line-interactive.
Line-interactive are off-line systems with an Automatic...
do not switch off the UPS!!!
it needs power to keep the batteries charged.
IMV NetPro UPS systems have to feature that when it is switched off by the power switch the unit still charges
its batteries: fans are spinning...
Harry
Phone system?
What is the load of this phone system?
Has the UPS a feature like no-load shutdown
which might be set at 5 % of its maximum power?
Try to disable the no-load shutdown feature of the UPS
first.
Harry
http://www.geindustrial.com/industrialsystems/gede/index.html
I used to work for Victron 8 years as a MATCH / NetPro
specialist.
What model do you have?
Harry
With normal charging reckon with a 1 : 20 ratio.
one hour discharge -> 20 hours charging.
Go for the MATCH series of GE IMV with boost charge.
http://www.geindustrial.com/industrialsystems/gede/index.html
Have a go at the RunTime Calculator
http://www.geindustrial.com/industrialsystems/gede/index.html
S: 5082VA
P: 5082 * 0.6 = 3049,2 W
Autonomy: 1 hour
UPS model:
Brand: General Electric IMV
Model: LanPro 10-11 with a total Ah value of 26 Ah.
This model is a True On Line (or: VFI = Voltage...
This site uses cookies to help personalise content, tailor your experience and to keep you logged in if you register.