  1. DLynn908

    Brand new Fortron EP650VA constantly in bypass mode.

    Its sounds like you may a line interactive UPS. You can test function by unplugging the the UPS and seeing if your computer stays up. Make sure you have saved everything and have your computer in a state where it will not be negatively affected by a loss of power. These smaller UPS sytems...
  2. DLynn908

    APC Symmetra 12KVA Power Array

    Make sure you wire the battery modules properly. Not just polarity but there is a battery connection midway through the string that must done properly otherwise you will get an alarm and it will trip your system to bypass. Good luck Don
  3. DLynn908

    UPS backup solution... im lost. need advice

    I would suggest an APC symmetra. They are scalable up to 16kva N+1. They also cn hold up to 4 strings of batteries in the main frame. Your 9kw is 11kva. This is the max current draw. Your constant load will will be less. The symmetra is a very popular UPS and is Modular. 90% of the parts...
  4. DLynn908

    Best Fortress LI660VA Blinking Display and No Power

    Since it is an older UPS, I would waste your money or time replacing batteries. You can get a brand new one inexpensively. with smaller ups, only replace the batteries once then buy a new one. You'll save yourself alot of head aches. Good Luck
  5. DLynn908

    UPS Toshiba 1400 series - Batteries replacement procedure

    You do not need to completely power down the UPS. You can transfer the load to bypass and replace the batteries. If there is a battery breaker you should be able to open that breaker and replace them. Just make sure your voltage and polarity are correct. Good Luck
  6. DLynn908

    Can you recommend a good “smart” UPS battery?

    APC is the leader in smaller UPS systems. I would check them first. www.apcc.com Good Luck
  7. DLynn908

    SmartUPS SUI1400INET Hotswappable?

    APC tends to overcharge the batteries so watch bulging batteries. If you cannot remove the batteries due to bulging you need to drill out and replace the rivets. Good Luck
  8. DLynn908

    Operating Fridge on UPS

    Using any refrigerator on a UPS is a bad Idea. I have had several calls about UPS' overloading due to A fridge or a laser printer being on the output. When the compressor turns on the inrush current shoots up and the UPS cant handle that much current rise. Good Luck
  9. DLynn908

    Battery life on UPS

    APC products tend to over charge the batteries. These type batteries last 3-5 years as an industry standard. Since APC overcharges the batteries i would replace them every 3 years. When you Charge a battery with a higher voltage the positive plate swell and make the cases bulge. When this...
  10. DLynn908

    Clarification on dual power supplies.

    The idea behind having dual power supplies on a server is to lessen the chance of failures. One input should be plugged into a properly sized UPS and the other should be plugged into a Utility Source. If either one fails the other should pick up the load. Your primary input should be plugged...
  11. DLynn908

    Delaying windows start up after AC in and server reboot

    YOu would have to do this through you computer. The UPS regardless of what brand, does turn on one plug at a time. Its either on Inverter, bypass or off. UPS' are an all or nothing type of device. Good luck
  12. DLynn908

    Symmetra Extended Frame error

    HI, The E7 Error means that the PCB on the back of your Extended run cabinet in faulty. You can pull it out by loosen 4 screws on the back of the frame and reseat it. If the problem persists then the PCB requires replacement. The part # is SYXRCC. Good luck