Thanks all for the input.
Vendor was supposed to install a new MH and duct system with four 4" ducts. Two were supposed to be spare 4" ducts for future expansion, one 4" with fiber inside inner duct and one 4" duct with the copper.
End result, two completely full 4" ducts of inner duct, one...
Is there a standard that requires fiber to be in inner duct in its own duct separate from copper cables? We have a contractor that pulled 148 strands dialectic fiber and 400 pair copper through same duct bank and want him to separate them. He pulled inner duct as part of the project but did not...