Tek-Tips is the largest IT community on the Internet today!

Members share and learn making Tek-Tips Forums the best source of peer-reviewed technical information on the Internet!

  • Congratulations Mike Lewis on being selected by the Tek-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. Mike_Wade

    Trouble interfacing CS1000 to Simplex 5110 for paging

    The Simplex system is used be security as well as zone paging, they only want to be able to do the all call from the CS1000 according to the documentation i found most of the commands for this system start with the "#" sign which i find very strange. however if looks like i have it in a workable...
  2. Mike_Wade

    Trouble interfacing CS1000 to Simplex 5110 for paging

    I can with MANO= YES I just change the following timers in the RDB OOD = 1 LEXT = 100 now after I get the tone, if i dial the #110 i get confirmation tone and can page if i pause for a fraction of a second between "#" and the "110" this may actually work
  3. Mike_Wade

    Trouble interfacing CS1000 to Simplex 5110 for paging

    FTR_DATA **DAPC**PREFIX TABLE NO: 00 ** UNKN**INTL**NATL**ESPN**LOCL**ELOC**ECDP** UNKN* E164* 00 0 PRIV* E163* 00 0 TELX* X121* NATL* OPT AHA BIND BIXA BLA CFF CFRD COX CPA CTD DBD DNX DSX HTU HVD XBL IC1 XDP XLF IHD XTG FKA LOD LRA MCI MWUD...
  4. Mike_Wade

    Trouble interfacing CS1000 to Simplex 5110 for paging

    With MANO = NO 1. dial 1721 2. get tone from page controller 3. dial #110 4. does not break tone, can't page if i wait several seconds after getting the tone before dialing then it breaks the tone gives confirmation tone and i can page still a delay
  5. Mike_Wade

    Trouble interfacing CS1000 to Simplex 5110 for paging

    When I do an enhanced trace if i dial the "#110" after the call shows "Established" i get confirmation tone and can page. dialing "##110" does not work If I dial "#110" as soon as i hear dial tone, the "#" breaks the dial tone however I do not get the confirmation tone and can't page. Enhanced...
  6. Mike_Wade

    Trouble interfacing CS1000 to Simplex 5110 for paging

    no it is CTD I changed it to UNR however there is still a delay before I can dial the #110 and have it work.
  7. Mike_Wade

    Trouble interfacing CS1000 to Simplex 5110 for paging

    I am having trouble interfacing to a Simplex 5110. i have programed a WAT route with a Trunk on a XUT card. See RDB and TN below: when i dial the access code for the route i get dial tone from the Simplex system, i need to be able to dial "#110" if it works correctly i would get a confirmation...